Short Circuit Impedance Calculation | IEC60909

Short circuit impedance calculation techniques based on IEC 60909 with correction factors for synchronous generators, power supply units, and transformers.

Determining the current paths whether ‘non-meshed’ or ‘meshed’ and the proximity of the fault, ‘far from’ or ‘near’ generators are prerequisites in the calculation of short circuit currents in IEC 60909. Prior to this is the determination of the impedances of the electrical equipment. For many, the short circuit impedance calculation is a straightforward process but in IEC 60909, the determination of impedances for certain equipment requires a slightly different approach. This is especially useful in the calculation of short circuit currents prescribed in the standard.

Network Feeders

Network feeders are usually represented by the initial symmetrical short circuit MVA, SkQ, or the initial symmetrical short circuit current, IkQ. With the nominal voltage at point Q (UnQ shown in the figure), the impedance can be calculated using,

If the short circuit RQ/XQ ratio is available, the reactance XQ can be calculated using,

If no short circuit RQ/XQ ratio information is available, the resistance RQ and reactance XQ can be approximated using the following relationship,

For networks operating at a nominal voltage greater than 35kV, setting the impedance equal to the reactance is usually sufficient.

It is also possible to use the above techniques in cases where the short circuit is fed through a transformer by introducing the transformation ratio such that

Synchronous Generators

For synchronous generators, the following information is usually available.

  1. Rated Apparent Power, SrG
  2. Rated Voltage, UrG
  3. Rated Power Factor, cos φrG
  4. Per unit Subtransient Reactance, x”d

The generator reactance can be determined from x”d using

To determine RG, the following approximations are fairly accurate.

RG = 0.05X”d, when UrG ≥ 1kV and SrG ≥ 100MVA

RG = 0.07X”d, when UrG ≥ 1kV and SrG ≤ 100MVA

RG = 0.15X”d, when UrG < 1kV

The generator subtransient impedance can be calculated using

Correction Factor for Generators (KG)

The voltage correction factors presented in our introductory discussion on IEC 60909 were intended to account for the system pre-fault conditions. Generally, voltage variation in power systems falls within ±5% to ±10% of the system nominal voltages. The calculation of maximum short-circuit current using applicable voltage factors, however, may not be sufficiently applicable to generators or power station units especially considering their subtransient behavior, i.e., equivalent voltage source cVn is used instead of substransient voltage E”. Accordingly, IEC 60909 introduced impedance correction factors specifically for generators and power station units.

The impedance correction factor for generators directly connected to the system can be calculated using,

where

ZGK is the generator corrected impedance

ZG is the generator subtransient impedance

KG is the generator impedance correction factor

Cmax is the voltage correction factor

UrG is the generator rated voltage

x”d is the generator per unit subtransient reactance

φrG is the phase angle between IrG and UrG/ 3

Correction Factor for Power Supply Unit (KPSU)

For generators with a dedicated transformer, a single correction factor is applied to the sum of their impedances. It is as if the generator and its dedicated transformer are treated as one unit.

where

ZPSU is the power supply unit corrected impedance

ZG is the generator subtransient impedance in ohms

ZrTHV is the transformer rated impedance referred to the HV side in ohms

tr is the transformer rated voltage ratio, VHV/VLV

KPSU is the power supply unit impedance correction factor

Cmax is the voltage correction factor

UnQ is the nominal system voltage

UrG is the generator rated voltage

x”d is the generator per unit subtransient reactance

xT is the transformer per unit reactance

φrG is the phase angle between IrG and UrG/ 3

Two-Winding Transformers

The impedance of two-winding transformers are calculated as follows:

where

ZT is the transformer positive sequence impedance

ukr is the transformer short circuit voltage at rated current

UrT is the transformer rated voltage

SrT is the transformer rated apparent power

RT is the transformer positive sequence resistance

PkrT is the transformer total winding losses at rated current

IrT is the transformer rated current

XT is the transformer positive sequence reactance

Correction Factor for Transformers (KT)

As with synchronous generators, transformer impedance correction factor can be calculated using,

where

ZKT is the transformer corrected impedance

ZT is the transformer positive sequence impedance

KT is the transformer impedance correction factor

Cmax is the voltage correction factor

xT is the transformer per unit reactance

UrT is the transformer rated voltage

SrT is the transformer rated apparent power

XT is the transformer reactance in ohms

It is important to note that the short circuit impedance calculation presented in this article are chosen based on the author’s perspective on the topic. The readers are encouraged to review the calculations prescribed in IEC 60909.

References

IEEE Std 551-2006 [The Violet Book]: Recommended Practice for Calculating AC Short Circuit Currents in Industrial and Commercial Power Systems. (2006). S.I.: IEEE.

BS EN 60909-0:2001: Short-circuit currents in three-phase a.c. systems Part 0: Calculation of currents (2002).

Kaskci, I. (2002). Short Circuit in Power Systems: A Practical Guide to IEC 60909. Weinheim, Germany: Wiley-VCH Verlag-GmbH.

pacbasics

View Comments

Share
Published by
pacbasics
Tags: IEC 60909

Recent Posts

2 Key Metrics in Overcurrent Protection: Why Time-Current Curves and Coordination Time Intervals Matter More Than You Think

TCC and CTI are the two most common acronyms in overcurrent protection coordination. Understanding Time-Current…

4 weeks ago

Transformer Tertiary Winding Basic Application

Tertiary winding in transformers have been widely used in the transmission and distribution of electricity…

5 years ago

How Do Reclosers Work? Settings and Operation

Photo Credit: NOJA Power Reclosers, otherwise known as autoreclosers (derived from "automatic reclosing" capability) or…

5 years ago

Impedance-Based Fault Location | A Step-by-Step Guide

Impedance-based fault location is widely used throughout the power transmission and distribution industry. In fact,…

5 years ago

Distance Relaying Fundamentals | What is Apparent Impedance?

In our introductory article on distance relaying, we presented a simple apparent impedance calculation for…

5 years ago

ETAP Star Coordination on Focus | Detailed Example

The main objective of any protection system is to interrupt short-circuits as fast as possible.…

6 years ago