Circuit Breaker Short-Circuit Duty Calculation | IEC60909

Circuit breaker short-circuit duty calculation is a very important step in our discussion on IEC 60909. We had just completed our discussion on the basic concepts of IEC 60909. We started with the introduction of IEC 60909 by defining the common terms used in the standard and how they compare to the terms in the ANSI-approved standards.

Next, we introduced the concept of ‘meshed’ and ‘non-meshed’ networks, how to identify them, and how important they are in the calculation of short-circuit currents. Then we introduced another important concept in IEC 60909 which is the ‘far from’ and ‘near’ generator short-circuits where we dived deeper into the calculation of short-circuits by introducing multiplying factors, how and when to use them.

Lastly, we took a step back and presented a discussion on how IEC 60909 determines the short-circuit impedances for common network components.

In this article, we will reinforce the concepts presented though a simple application example. Circuit breaker short-circuit duty calculation will be presented in a step-by-step approach. For comparison, we will use the same sample network from our application example for the ANSI-approved standard.

Sample Network

Figure 1 shows a network with two sources, one is network feeder through a transmission line and the other is a synchronous generator. Our faulted point is the bus where the synchronous generator is directly connected.

Figure 1. Sample Network Diagram

Calculation of Short-Circuit Impedance

We will start by creating an impedance diagram using the concepts that we learned from our previous discussions.

Network Feeder

Network feeders are usually represented by the initial symmetrical short circuit MVA, SkQ, or the initial symmetrical short circuit current, IkQ”. With the nominal voltage UnQ, the impedance can be calculated as follows.

In this example, we will be calculating the maximum short-circuit duty. Given this, we will set the voltage correction factor cmax = 1.1. Refer to this link for the list of voltage correction factors used in IEC 60909.

Next, we calculate the reactance based on our computed ZQ and the given X/R ratio.

From there, it is easy to calculate RQ.

Transmission Line

The method in calculation of transmission lines impedance was omitted in our previous discussion since its determination is the same throughout different standards and is available in different power system analysis books. It is important to note, however, that since we are dealing with the calculation of the maximum short-circuit currents, it is necessary to adjust the transmission line resistance to a temperature of 20°C as prescribed in IEC 60909.

With the reactance equal to

The impedance of the transmission line can be easily calculated using

The total impedance from the network feeder to the fault point can be calculated from the sum of the feeder and transmission line resistance and reactance, therefore,

and the R/X ratio

Synchronous Generator

The easiest way to determine the generator impedance is to start with the calculation of its reactance using,

Next is to determine the generator resistance. Since the generator in this example has a rated apparent power of 5.952MVA, we can approximate its resistance using,

The generator impedance is calculated using,

To account for the generator substransient behavior, IEC 60909 has recommended impedance correction factors. For generators this is,

The corrected impedance is calculated using,

The impedance diagram is shown in figure 2.

Figure 2. Impedance Diagram

Calculation of Initial Symmetrical Short-Circuit Currents

Network Feeder

The calculation of initial symmetrical short-circuit current contribution from the network feeder through the transmission can be calculated using,

Synchronous Generator

The same process is done to calculate the initial symmetrical short-circuit current contribution from the generator.

Total Initial Symmetrical Short-Circuit Current

The total initial symmetrical short-circuit current is calculated as follows,

Calculation of the Peak Short-circuit Current

Network Feeder

The calculation of the peak short-circuit current contribution from the network feeder through the transmission can be calculated from

The crest factor is determined using

The peak short-circuit current contribution from the network feeder is

Synchronous Generator

The same process is done to calculate the peak short-circuit current contribution from the generator.

Total peak short-circuit current

The total peak short-circuit current is calculated as shown

Calculation of Symmetrical Short-circuit Breaking Current

Network Feeder

Since network feeders’ short-circuit contribution are considered ‘far-from’ generator short-circuit, the symmetrical short-circuit breaking current is equal to the initial symmetrical short-circuit current.

Synchronous Generator

For a synchronous generator, it is necessary to determine first whether the short-circuit is ‘far-from’ or ‘near’ generator. We can check the ratio of its initial symmetrical short-circuit current contribution to its rated current if its greater than 2.

Since I”kG/IrG is greater than 2, the synchronous generator in this example is a ‘near’ generator.

To calculate the symmetrical short-circuit breaking current contribution of the generator, a factor µ is introduced.

IEC 60909 has provided the equations to calculate µ based on a particular minimum time delay. For this example, let us assume a minimum time delay of 0.05s.

Calculating for the generator symmetrical short-circuit breaking current contribution we get,

Total Symmetrical Short-Circuit Breaking Current

The total symmetrical short-circuit breaking current is calculated as shown

Calculation of Asymmetrical Short-circuit Breaking Current

If the calculation of the asymmetrical short-circuit breaking current is of interest, the following procedures apply.

Determine the aperiodic DC component of the initial symmetrical short-circuit current using the following equation,

Network Feeder

Synchronous Generator

For synchronous generators, the calculation of the aperiodic DC component requires an X/R ratio provided by the manufacturer. Unfortunately, the approximation of RG to get the X/R ratio cannot be used. For this example, based on the manufacturer’s data, the X/R ratio for the given generator is 19.

Calculate the total aperiodic DC component using,

Total Asymmetrical Short-Circuit Breaking Current

Calculate the total asymmetrical short-circuit breaking current using,

Calculation of Steady-State Short-Circuit Current

Network Feeder

Since network feeders’ short-circuit contributions are considered ‘far-from’ generator short-circuit, the steady-state short-circuit current is equal to the initial symmetrical short-circuit current.

Synchronous Generator

Steady-state short-circuit current for ‘near’ generator short-circuits is normally lower in magnitude than the symmetrical short-circuit breaking current. The calculation of the steady-state short-circuit current is rather straightforward in that it depends only on the generator rated current and the excitation voltage.

Since the circuit breaker short-circuit duty is of interest here, the maximum steady-state short-circuit current is calculated using,

The multiplying factor λmax depends on whether the generator is a turbo or salient-pole generator and the ratio of the maximum excitation voltage to the excitation voltage under normal load conditions (series 1 or 2).

The generator in this example is a turbogenerator with a maximum excitation voltage of 1.3 times its rated. Therefore, we will be using the series 1 curve for turbo generators. From the manufacturer’s data, the saturated value of synchronous reactance is 1.55.

Figure 3. Series 1 Curve for Turbo Generators

Based on the given curve, the multiplying factor λmax is determined as shown

The steady-state short-circuit current contribution from the generator is calculated as shown

Total Steady-State Short-Circuit Current

The total steady-state short-circuit current is calculated as shown

And that’s about it.

Circuit breaker short-circuit duty calculation based on IEC 60909 is quite lengthy and would take a lot of time when done manually. A good computer software will surely help in the analysis!

In our next article, we’ll present the IEC 60909 analysis procedure using ETAP software.

References

IEEE Std 551-2006 [The Violet Book]: Recommended Practice for Calculating AC Short Circuit Currents in Industrial and Commercial Power Systems. (2006). S.I.: IEEE.

BS EN 60909-0:2001: Short-circuit currents in three-phase a.c. systems Part 0: Calculation of currents (2002).

Kaskci, I. (2002). Short Circuit in Power Systems: A Practical Guide to IEC 60909. Weinheim, Germany: Wiley-VCH Verlag-GmbH.

ETAP Enterprise Solution for Electrical Power Systems Online Help

pacbasics

View Comments

  • Great article. However, I have question regarding the summation of short-circuit currents from short-circuit sources.
    Are the short-circuit currents added vectorially (phasor form) or just adding the magnitudes of the short-circuit current?
    Thank you

    • Hi Elvin,

      Thank you for your interest in this topic.

      As stated in the standard, for non-meshed sources, the total short-circuit current is calculated as the arithmetic sum of the individual source contribution. We hope this answers your question.

      Kind Regards,

      PAC Basics Team

Share
Published by
pacbasics

Recent Posts

Transformer Vector Groups Explained: The Math Behind YNd11 Connections

In our previous article on transformer vector groups, we mentioned the importance of the delta…

4 months ago

2 Key Metrics in Overcurrent Protection: Why Time-Current Curves and Coordination Time Intervals Matter More Than You Think

TCC and CTI are the two most common acronyms in overcurrent protection coordination. Understanding Time-Current…

9 months ago

Transformer Tertiary Winding Basic Application

Tertiary winding in transformers have been widely used in the transmission and distribution of electricity…

5 years ago

How Do Reclosers Work? Settings and Operation

Photo Credit: NOJA Power Reclosers, otherwise known as autoreclosers (derived from "automatic reclosing" capability) or…

6 years ago

Impedance-Based Fault Location | A Step-by-Step Guide

Impedance-based fault location is widely used throughout the power transmission and distribution industry. In fact,…

6 years ago

Distance Relaying Fundamentals | What is Apparent Impedance?

In our introductory article on distance relaying, we presented a simple apparent impedance calculation for…

6 years ago