Short Circuit Impedance Calculation | IEC60909

Short circuit impedance calculation techniques based on IEC 60909 with correction factors for synchronous generators, power supply units, and transformers.
Determining the current paths whether ‘non-meshed’ or ‘meshed’ and the proximity of the fault, ‘far from’ or ‘near’ generators are prerequisites in the calculation of short circuit currents in IEC 60909. Prior to this is the determination of the impedances of the electrical equipment. For many, the short circuit impedance calculation is a straightforward process but in IEC 60909, the determination of impedances for certain equipment requires a slightly different approach. This is especially useful in the calculation of short circuit currents prescribed in the standard.
Network Feeders
Network feeders are usually represented by the initial symmetrical short circuit MVA, SkQ”, or the initial symmetrical short circuit current, IkQ”. With the nominal voltage at point Q (UnQ shown in the figure), the impedance can be calculated using,

If the short circuit RQ/XQ ratio is available, the reactance XQ can be calculated using,

If no short circuit RQ/XQ ratio information is available, the resistance RQ and reactance XQ can be approximated using the following relationship,


For networks operating at a nominal voltage greater than 35kV, setting the impedance equal to the reactance is usually sufficient.

It is also possible to use the above techniques in cases where the short circuit is fed through a transformer by introducing the transformation ratio such that

Synchronous Generators
For synchronous generators, the following information is usually available.
- Rated Apparent Power, SrG
- Rated Voltage, UrG
- Rated Power Factor, cos φrG
- Per unit Subtransient Reactance, x”d
The generator reactance can be determined from x”d using

To determine RG, the following approximations are fairly accurate.
RG = 0.05X”d, when UrG ≥ 1kV and SrG ≥ 100MVA
RG = 0.07X”d, when UrG ≥ 1kV and SrG ≤ 100MVA
RG = 0.15X”d, when UrG < 1kV
The generator subtransient impedance can be calculated using

Correction Factor for Generators (KG)
The voltage correction factors presented in our introductory discussion on IEC 60909 were intended to account for the system pre-fault conditions. Generally, voltage variation in power systems falls within ±5% to ±10% of the system nominal voltages. The calculation of maximum short-circuit current using applicable voltage factors, however, may not be sufficiently applicable to generators or power station units especially considering their subtransient behavior, i.e., equivalent voltage source cVn is used instead of substransient voltage E”. Accordingly, IEC 60909 introduced impedance correction factors specifically for generators and power station units.

The impedance correction factor for generators directly connected to the system can be calculated using,


where
ZGK is the generator corrected impedance
ZG is the generator subtransient impedance
KG is the generator impedance correction factor
Cmax is the voltage correction factor
UrG is the generator rated voltage
x”d is the generator per unit subtransient reactance
φrG is the phase angle between IrG and UrG/ 3
Correction Factor for Power Supply Unit (KPSU)
For generators with a dedicated transformer, a single correction factor is applied to the sum of their impedances. It is as if the generator and its dedicated transformer are treated as one unit.



where
ZPSU is the power supply unit corrected impedance
ZG is the generator subtransient impedance in ohms
ZrTHV is the transformer rated impedance referred to the HV side in ohms
tr is the transformer rated voltage ratio, VHV/VLV
KPSU is the power supply unit impedance correction factor
Cmax is the voltage correction factor
UnQ is the nominal system voltage
UrG is the generator rated voltage
x”d is the generator per unit subtransient reactance
xT is the transformer per unit reactance
φrG is the phase angle between IrG and UrG/ 3
Two-Winding Transformers
The impedance of two-winding transformers are calculated as follows:



where
ZT is the transformer positive sequence impedance
ukr is the transformer short circuit voltage at rated current
UrT is the transformer rated voltage
SrT is the transformer rated apparent power
RT is the transformer positive sequence resistance
PkrT is the transformer total winding losses at rated current
IrT is the transformer rated current
XT is the transformer positive sequence reactance
Correction Factor for Transformers (KT)
As with synchronous generators, transformer impedance correction factor can be calculated using,



where
ZKT is the transformer corrected impedance
ZT is the transformer positive sequence impedance
KT is the transformer impedance correction factor
Cmax is the voltage correction factor
xT is the transformer per unit reactance
UrT is the transformer rated voltage
SrT is the transformer rated apparent power
XT is the transformer reactance in ohms
It is important to note that the short circuit impedance calculation presented in this article are chosen based on the author’s perspective on the topic. The readers are encouraged to review the calculations prescribed in IEC 60909.
References
BS EN 60909-0:2001: Short-circuit currents in three-phase a.c. systems Part 0: Calculation of currents (2002).
Kaskci, I. (2002). Short Circuit in Power Systems: A Practical Guide to IEC 60909. Weinheim, Germany: Wiley-VCH Verlag-GmbH.
One thought on “Short Circuit Impedance Calculation | IEC60909”