Abstract: There are a lot of methods that can be used for short-circuit current calculation. One method was previously discussed here and is based on the guidelines presented in IEC 60909. This article deals with an alternative method for the short-circuit current calculation so-called the MVA method. This method is simple, quick, and easy to remember. It is also sufficiently accurate for engineers in practice for basic estimation of fault levels at any point in an electrical network.
Keywords: short-circuit current, the MVA method, calculation methods
The determination of the level of short-circuit current at any point of an electrical network can be of interest because of several reasons, e.g.:
In most practical applications, it is not necessary to know the exact time course of short-circuit currents. A simplified calculation is often sufficient. There are several methods for the calculation of short-circuit currents. These can be divided into numerical and numeric-graphical methods. Some of them are listed below:
This method can be used when the task is limited only to finding the short-circuit current at the short-circuit location. This method is popular because of its simplicity and relative accuracy. The method consists of the application of special curves that give the value of the a.c. component of the short-circuit current in any moment of the short-circuit fault,
This is a simple graphical method that consists of subtracting the necessary parameters of the electrical system elements (impedances) from the graphs that were pre-printed on the sheets, separately for each voltage level. The disadvantage of nomograms is their limited use only for radial networks and the fact that the method accuracy is directly dependent on the accuracy of reading from the graphs drawn.
Also known as the Impedance Method. The disadvantage of this method is it is cumbersome if the system under investigation contains several voltage levels,
This method is no better in terms of manual calculations than the previous method since it involves a number of relationships and bonds associated with reference values, which can often cause errors in the calculation procedure,
This method is used very often but requires knowledge of steady-state conditions before the short-circuit occurrence, which reduces its applicability for general and fast calculations.
The MVA method is an alternative to the earlier mentioned methods. It is based on a mathematical modification of the ohmic method. The first step of calculation procedure is to convert classic single-line diagram of the power network to an equivalent MVA diagram. The next steps are based on the simplification of an equivalent MVA diagram to one final value of MVA at the fault point (this represents short-circuit MVA at the fault point).
This method has the following simplifications:
Advantages of this method are the following:
Let’s consider following a simple 22kV electrical network according to Figure 1 (taken from [3] and modified). Let us assume that the industrial power network is connected through the power line V1 and supplied from the 22 kV external distribution network. For sake of simplicity, we consider only one synchronous generator, TG, and one synchronous motor, SM1 in the industrial power network. The task is to find out the value of initial symmetrical three-phase short-circuit current at 6.6 kV busbar.
As mentioned earlier, the first step is the calculation of the MVA level of each component and converting the single line diagram to its equivalent MVA diagram.
For overhead power lines, the short-circuit MVA can be calculated directly from the impedance in form Zv=R+jX, therefore we can write
An advantage of this method is that the short-circuit voltage of the transformer (percentage value of reactance) is given directly in relationship with the nominal apparent power of the transformer. The same is valid for motors and generators as well.
The equivalent MVA diagram is shown in figure 2.
Now we can reduce the equivalent MVA diagram. For elements connected in series the equivalent value of initial symmetrical short-circuit power is equal to the sum of inverted MVA values of elements.
For example, the equivalent MVA at branch A (consisting of network feeder, transformer T1 and power line V1) is
For elements connected in parallel, the final value of initial symmetrical short-circuit power is equal to the sum of MVA values of elements.
The electrical network equivalent MVA can be obtained from the sum of three parallel branches A, B, and C.
The graphical representation of industrial power network reduction is shown in figure 3.
Finally, the initial symmetrical short-circuit current at the fault point can be calculated from the equivalent network MVA.
In order to validate the accuracy of the MVA Method, we will calculate the initial symmetrical short-circuit current at the fault point using the calculation method based on IEC 60909. For simplicity, resistance will be neglected.
The equivalent short-circuit impedance at the fault point is calculated to be
Calculating the short-circuit MVA,
Finally, the initial symmetrical short-circuit current at the fault point can be calculated from the equivalent network MVA.
If the value of initial symmetrical short-circuit current is known, the peak short-circuit current can be determined using
A comparison of the results between the two methods is shown in the following table. The results based on IEC 60909 calculation method will be used as a reference.
It can be seen that the MVA method gives results with sufficient accuracy.
The methods calculation short-circuit currents vary in complexity and the amount of effort put into. The MVA method is known to be simple, quick, and easy, and is sufficiently accurate for engineers in practice for basic estimation of fault levels at any point in an electrical network.
[1] Jaffari, H.: Fault Current Calculation. Power System Review: Module 6. Northeast Public Power Association, 2013.
[2] Lee Wai, M., Pang, J.M.: Electrical Fault Level Calculations Using the MVA Method. Dostupné na internete: < http://www.jmpangseah.com>
[3] Kakilli, A.: System Analysis with the MVA Method for Symmetrical Three-Phase Faults. TEM Journal, vol2 no1, 2013.
[4] Máslo, K., Novák, J., Doležal, J.: Analysis of short-circuit currents. In Symposium Elektroenergetika. Stará Lesná, Slovakia, 2001.
[5] Pauza, J.: Short-circuits in electrical networks. SNTL Prague, Czech Republic, 1970.
[6] Máslo, K. et al.: Control and stability of power system. ČEPS and Energy managers’ association. Prague, Czech Republic, 2013. ISBN 978-80-260-4461-1
[7] STN IEC 60909 – 0: Short-circuit currents in three-phase a.c. systems. Part 0: Calculation of currents. Valid from 1.10.2016.
TCC and CTI are the two most common acronyms in overcurrent protection coordination. Understanding Time-Current…
Tertiary winding in transformers have been widely used in the transmission and distribution of electricity…
Photo Credit: NOJA Power Reclosers, otherwise known as autoreclosers (derived from "automatic reclosing" capability) or…
Impedance-based fault location is widely used throughout the power transmission and distribution industry. In fact,…
In our introductory article on distance relaying, we presented a simple apparent impedance calculation for…
The main objective of any protection system is to interrupt short-circuits as fast as possible.…
View Comments
Thank you.
In getting the Zs of 22kV External Distribution Network by the IEC 60909 Method, I might have missed where we get the constant C and the value assigned to it as 1.1. Please advise.
Hi Louie,
I hope this is not too late but to answer your question, the constant C is taken from the voltage factors recommended in the IEC 60909. This is in order to account for the system prefault conditions. You can refer to the table of voltage factors from this link.
Kind Regards,
PAC Basics Team
An excellent and very helpful article.Missing are only the calculations to detemine the value of the total impedance Zfault=0,353 Ω,which I think would be very useful.Kindly advise
Many thanks
Hi Athan,
Thank you for your interest in the topic. Actually, the total impedance, Zfault, is the equivalent impedance i.e. series/parallel combination of the impedances upstream. So in this case, it is the series combination of the source, line, transformer impedances, this, in parallel with the generator and motor impedances.
Dear Sir,
Thank you very much for your reply
Regards
Thank you
Nice article
You're welcome!
Informative article re calculating fault currents using MVA method. Thanks
straight forward. clear and easy to follow.
thanks much.
Informative article. Thanks
Nice article. Thank you
Nice article and very informative.
Great and useful article,, thank you.
You're welcome! :)